Pressure Relief Valve Sizing Calculator — API 520 Required Effective Area and API 526 Orifice Letter for Gas, Steam, Liquid and Two-Phase Relief

Configuration

Fluid properties come from the CoolProp tables in Thermodynamics Land (gases, steam and liquids) or this site's own digitized liquid data (Multi-Fluid Property Charts). Every property box can be typed over; blank boxes use the fluid data (shown in grey). Pick "Manual entry" to type all of them yourself.

Warnings & Status
No results yet
Set Pressure i The gauge pressure at which the valve starts to open. For the first (or only) device it may not exceed the MAWP of the equipment it protects.
psig
barg
kPag
MAWP i Maximum allowable working pressure of the protected vessel or system. The allowable accumulation (10, 16 or 21 %) is a percentage of MAWP, not of set pressure.
psig
barg
kPag
Total Back Pressure (P₂) i Pressure at the valve outlet while it flows: superimposed back pressure (present before the valve opens) plus built-up back pressure (from flow in the discharge piping). Use 0 for a valve venting straight to atmosphere.
psig
barg
kPag
Barometric Pressure
psia
kPa
Use the value for the site elevation.
Relieving Temperature (T₁) i Temperature of the fluid at the valve inlet at relieving conditions (not the normal operating temperature).
deg F
deg C
Kelvin
deg R
Required Relieving Rate (W)
lb/h
kg/h
or gas volume at standard conditions
scfm
Nm³/min
scfm at 14.7 psia and 60 °F; Nm³/min at 101.325 kPa and 0 °C. Converted to mass flow with M, using the factors in API 520 eq. (3) and (6).
Required Relieving Rate (Q)
GPM
L/min
m³/hr
Volume flow at the flowing temperature.
Gas Properties at Relief i k is the ideal-gas ratio of specific heats at the relieving temperature, as API 520 asks (5.6.2.4); a real-gas Cₚ/Cᵥ from a simulator can undersize the valve. Z is the compressibility at relieving pressure and temperature. Leave blank to use the fluid data.
k
Z
M
Steam Condition
KSH
Saturation temp. at P₁ (°F)—
Liquid Properties at Relief
G
Viscosity at T₁
Two-Phase Specific Volume i v₀ is the two-phase specific volume at the valve inlet. v₉ is the specific volume after flashing to 90 % of the inlet pressure (absolute), from an isentropic flash (isenthalpic is acceptable for low-quality mixtures far from the critical point). Both come from your process simulator's flash calculation.
v₀ at the inlet
ft³/lb
m³/kg
v₉ at 90 % of inlet pressure
ft³/lb
m³/kg
Coefficients i Blank boxes use the API 520 preliminary-sizing values (grey). K₞ for balanced-bellows valves and Kᵠ for balanced-bellows valves in liquid service come from the valve manufacturer; API 520 Figures 30 and 31 give typical curves when the make is not known.
Kd
Kb
Kw
Kc
Relieving Conditions
Max. accumulated pressure—
Allowable overpressure—
Relieving pressure P₁ (psia)—
Relieving pressure P₁ (kPa)—
Back pressure P₂ (psia)—
Back pressure, % of set (gauge)—
Critical flow pressure Pcf (psia)—
Flow—
Sizing Factors
— 
Required Effective Area
 
Required area (in²)—
Required area (mm²)—
API 526 orifice letter—
Letter effective area—
Required / letter area—
Sizing equation (API 520)—
API 526 Orifice Letters
Letterin²mm²
Effective areas for preliminary sizing with the API 520 equations. Check the chosen valve's actual area and rated coefficient with the manufacturer.

Preliminary sizing with the API Standard 520 Part I (8th edition) equations and the API 526 effective orifice areas. The selected valve's certified capacity must still be checked with its actual area and rated coefficient of discharge.

Reference Guide — Relief Valve Sizing
01

What Sizing a Relief Valve Means

A pressure relief valve (PRV) opens when the pressure in a vessel or line reaches its set pressure and passes enough flow to stop the pressure rising past what the code allows. Sizing finds the smallest effective discharge area that passes the required relieving rate at the relieving pressure, then picks the standard orifice that is at least that big.

The steps on this page follow API Standard 520 Part I:

  • Find the worst-case relieving rate W (or Q) for the contingency: blocked outlet, control valve failure, fire and so on. API 521 lists the common causes. This page takes that rate as an input.
  • Fix the relieving pressure P₁ from the set pressure, MAWP and the allowable accumulation (card 02).
  • Calculate the required effective area A with the equation for the service: gas or vapor, steam, liquid or two-phase (cards 03 to 07).
  • Choose the API 526 orifice letter whose effective area is equal to or larger than A (card 08).
Pressure levels for a relief valve: operating pressure below set pressure, set pressure at or below MAWP, and the maximum accumulated pressure 10, 16 or 21 percent above MAWP; relieving pressure P1 is the accumulated pressure plus atmospheric pressure
Pressure levels for a single relief device
Preliminary sizing. The API 520 coefficients (Kd = 0.975 for gas and steam, 0.65 for liquid) and the API 526 effective areas are nominal values for choosing a valve size. They are not a particular valve's certified values. Once a valve is chosen, its rated capacity must be checked with that valve's actual orifice area and rated coefficient of discharge (API 520 5.2).
02

Set Pressure, Accumulation & Relieving Pressure

Accumulation is the pressure rise above MAWP allowed while the device relieves. Overpressure is the rise above the set pressure. When the set pressure equals MAWP they are the same; when the valve is set lower, the overpressure is larger.

Relieving pressure (absolute) \[ P_1 = P_{set} + \Delta P_{over} + P_{atm} = P_{accum,max} + P_{atm} \]

For liquids the sizing equation uses gauge pressures, so P₁ there is the set pressure plus the overpressure, without the atmospheric term.

When the MAWP is between 15 and 30 psig (103 and 207 kPag), the allowable accumulation for operating contingencies is 3 psi (21 kPa) for a single device and 4 psi (28 kPa) for multiple devices. This calculator uses the larger of that and the percentage.

ContingencyDeviceMax. set pressure, % MAWPMax. accumulated pressure, % MAWP
Operating, single deviceFirst100110
Operating, multiple devicesFirst100116
Operating, multiple devicesAdditional105116
FireFirst100121
FireAdditional105121
FireSupplemental110121
Set pressure and accumulation limits for ASME Section VIII vessels, from API 520 Part I Table 1.
Example (API 520 Table 2): MAWP 100 psig, set 100 psig, single device. Maximum accumulated pressure 110 psig, overpressure 10 psi, P₁ = 110 + 14.7 = 124.7 psia. With the valve set at 90 psig the overpressure is 20 psi and P₁ is the same.
03

Gas or Vapor: Critical & Subcritical Flow

Gas speeding up through the valve nozzle reaches the speed of sound when the outlet pressure is low enough. Below that critical flow pressure, lowering the back pressure further does not increase the flow, and the flow depends only on the inlet conditions.

Critical flow pressure ratio, eq. (1) \[ \frac{P_{cf}}{P_1} = \left(\frac{2}{k+1}\right)^{\frac{k}{k-1}} \]

If P₂ ≤ Pcf the flow is critical (choked):

Critical flow, eq. (2) USC / (5) SI \[ A = \frac{W}{C\,K_d\,P_1\,K_b\,K_c}\sqrt{\frac{T\,Z}{M}} \] \[ C = 520\sqrt{k\left(\frac{2}{k+1}\right)^{\frac{k+1}{k-1}}}\ \text{(USC)},\qquad C = 0.03948\sqrt{k\left(\frac{2}{k+1}\right)^{\frac{k+1}{k-1}}}\ \text{(SI)} \]

USC: A in², W lb/h, P₁ psia, T °R. SI: A mm², W kg/h, P₁ kPa, T K. M is the molecular weight. If k is not known, API 520 suggests C = 315 (0.0239), the value at k = 1, which is conservative.

If P₂ > Pcf the flow is subcritical. For conventional and pilot-operated valves the area is:

Subcritical flow, eq. (12) USC / (15) SI \[ A = \frac{W}{735\,F_2\,K_d\,K_c}\sqrt{\frac{Z\,T}{M\,P_1\,(P_1-P_2)}}\qquad A = \frac{17.9\,W}{F_2\,K_d\,K_c}\sqrt{\frac{Z\,T}{M\,P_1\,(P_1-P_2)}} \] \[ F_2 = \sqrt{\left(\frac{k}{k-1}\right) r^{2/k}\left[\frac{1-r^{(k-1)/k}}{1-r}\right]},\qquad r = \frac{P_2}{P_1} \]

Balanced-bellows valves are sized with the critical-flow equation and the manufacturer's Kb, even when the flow is subcritical (5.6.4.3).

Which k? Use the ideal-gas k at the relieving temperature. A real-gas Cₚ/Cᵥ at high pressure is not a good model of the isentropic expansion, and using it can undersize the valve (5.6.2.4). This page takes k and M from the CoolProp data at the lowest tabulated pressure (the ideal-gas limit) and Z from the density at P₁ and T₁. Where Z is below about 0.8 or above about 1.1, API 520 Annex B covers sizing for strongly non-ideal fluids.
04

Back Pressure & Valve Types

Simplified cross-sections of a conventional spring-loaded relief valve, where outlet pressure acts on the top of the disc, and a balanced-bellows valve, where a bellows shields the disc from outlet pressure
Conventional vs. balanced-bellows valve (simplified)

Conventional valve. Back pressure in the outlet pushes on the back of the disc. Superimposed back pressure raises the opening pressure, so the spring is set lower to suit (the cold differential test pressure). Built-up back pressure should stay under 10 % of the set pressure at 10 % overpressure; above that the valve can chatter. No Kb correction is used for gas at critical flow or for liquid (5.3.3.1.3).

Balanced-bellows valve. A bellows keeps the back pressure off the disc, so it can usually take a total back pressure up to about 50 % of the set pressure. High back pressure still reduces lift, so the capacity is corrected with Kb (gas and steam) or Kw (liquid) from the manufacturer (5.3.3.2).

Pilot-operated valve. Lift is not affected by back pressure; for gas at critical flow Kb = 1.0 (5.3.3.3).

Rupture disk upstream of a valve. The combination's capacity is multiplied by Kc: the certified value for that disk and valve pair, or 0.9 when the combination has no certified value (5.11.2).

05

Steam (Napier Equation)

Steam at critical flow is sized with the Napier equation rather than the general gas equation:

Steam, eq. (21) USC / (22) SI \[ A = \frac{W}{51.5\,P_1\,K_d\,K_b\,K_c\,K_N\,K_{SH}}\qquad A = \frac{190.5\,W}{P_1\,K_d\,K_b\,K_c\,K_N\,K_{SH}} \]
Napier correction, eq. (23) to (25) \[ K_N = 1.0 \quad (P_1 \le 1500\ \text{psia} = 10\,339\ \text{kPa}) \] \[ K_N = \frac{0.1906\,P_1 - 1000}{0.2292\,P_1 - 1061}\ \text{(psia)},\qquad K_N = \frac{0.02764\,P_1 - 1000}{0.03324\,P_1 - 1061}\ \text{(kPa)} \]

The second form applies from 1500 to 3200 psia (10 339 to 22 057 kPa).

KSH corrects for superheat. It is 1.0 for saturated steam at any pressure, and for superheated steam it comes from API 520 Table 9 by set pressure and temperature (15 to 3000 psig, 300 to 1200 °F). This page interpolates linearly between the table's rows and columns. Where the point falls next to a blank (“—”) cell of the table, there is no tabulated value to interpolate from, and the page asks for KSH.

Above 1200 °F, API 520 says to size steam with the gas equations (card 03).

Example (API 520 5.7.2): 153 500 lb/h saturated steam, set 1600 psig, 10 % accumulation. P₁ = 1774.7 psia, KN = 1.01, A = 1.705 in² (1100 mm²): a K orifice (1.838 in²).
06

Liquid Relief & Viscosity Correction

For valves with ASME capacity certification in liquid service, the liquid is treated as incompressible:

Liquid, eq. (28) USC / (29) SI \[ A = \frac{Q}{38\,K_d\,K_w\,K_c\,K_v}\sqrt{\frac{G_l}{P_1 - P_2}}\qquad A = \frac{11.78\,Q}{K_d\,K_w\,K_c\,K_v}\sqrt{\frac{G_l}{P_1 - P_2}} \]

USC: Q in US gal/min, P in psig. SI: Q in L/min, P in kPag. Gl is the specific gravity at the flowing temperature, referred to water at standard conditions. This page uses water at 60 °F (999.01 kg/m³), the same reference as the site's other fluid pages. For preliminary sizing Kd = 0.65.

Viscous liquids flow less than the equation predicts. API 520 sizes first with Kv = 1, takes the next larger standard orifice, finds its Reynolds number, and corrects the area by Kv. If the corrected area is larger than that orifice, the steps repeat with the next size up. This page runs that loop for you.

Reynolds number, eq. (31) to (34); Kv, eq. (30) \[ Re = \frac{Q\,(2800\,G_l)}{\mu\sqrt{A}}\ \text{or}\ \frac{12\,700\,Q}{U\sqrt{A}}\ \text{(USC)},\qquad Re = \frac{Q\,(18\,800\,G_l)}{\mu\sqrt{A}}\ \text{or}\ \frac{85\,220\,Q}{U\sqrt{A}}\ \text{(SI)} \] \[ K_v = \left(0.9935 + \frac{2.878}{Re^{0.5}} + \frac{342.75}{Re^{1.5}}\right)^{-1} \]

μ in centipoise, U in Saybolt universal seconds (the SSU forms are not recommended below 100 SSU). API 520 Figure 37 stops at Kv = 1.0, which the equation passes near Re = 105, so the page holds Kv at 1.0 there.

Example (API 520 5.8.2): 1800 gal/min crude, G = 0.90, 2000 SSU, set 250 psig, back pressure 0 to 50 psig on a balanced-bellows valve (Kw = 0.97). AR = 4.752 in², Re = 4525 on the P orifice, Kv = 0.964, A = 4.93 in²: a P orifice.
07

Two-Phase Relief: Omega Method

A liquid that flashes, or a mixture of liquid and vapor, can pass much less mass through a valve than the liquid equation predicts. API 520 Annex C gives Leung's omega method, a form of the homogeneous equilibrium model, for flashing or non-flashing two-phase flow with no non-condensable gas at the inlet. ω describes how fast the mixture expands as the pressure falls, from two specific volumes:

Omega parameter, eq. (C.12) \[ \omega = 9\left(\frac{v_9}{v_0} - 1\right) \]

v₀ is the specific volume at the inlet and v₉ is the specific volume at 90 % of the inlet pressure, from a flash calculation in a process simulator.

Critical pressure ratio, eq. (C.14) \[ \eta_c^2 + (\omega^2 - 2\omega)(1-\eta_c)^2 + 2\omega^2\ln\eta_c + 2\omega^2(1-\eta_c) = 0 \]

If Pc = ηcP₀ ≥ Pa (the back pressure), the flow is critical:

Mass flux, eq. (C.16) USC / (C.18) SI, and subcritical (C.17) / (C.19) \[ G = 68.09\,\eta_c\sqrt{\frac{P_0}{v_0\,\omega}}\ \text{(USC)},\qquad G = \eta_c\sqrt{\frac{P_0}{v_0\,\omega}}\ \text{(SI)} \] \[ G = \frac{\left\{-2\left[\omega\ln\eta_a + (\omega-1)(1-\eta_a)\right]\right\}^{1/2}}{\omega\left(\frac{1}{\eta_a}-1\right)+1}\sqrt{\frac{P_0}{v_0}},\qquad \eta_a = \frac{P_a}{P_0} \]
Area, eq. (C.20) USC / (C.21) SI \[ A = \frac{0.04\,W}{K_d\,K_b\,K_c\,K_v\,G}\qquad A = \frac{277.8\,W}{K_d\,K_b\,K_c\,K_v\,G} \]

USC: P psia, v ft³/lb, G lb/(s·ft²), W lb/h, A in². SI: P Pa, v m³/kg, G kg/(s·m²), W kg/h, A mm². For preliminary sizing Kd = 0.85. The subcritical USC form carries the same 68.09 factor.

No pressure relief valve has a certified two-phase capacity, and these methods have not been validated by test (API 520 C.1.1, 5.10.2). Treat the result as an estimate.
08

API 526 Orifice Letters

API 526 is the purchase specification for flanged steel relief valves. It names each orifice size by a letter, from D (smallest) to T (largest), and gives each letter an effective area to be used with the API 520 equations. The required area from the calculator is rounded up to the next letter.

Effective areas are not the area of any real valve. A manufacturer's valve with a given letter has its own actual orifice area and rated coefficient of discharge, chosen so that its certified capacity meets or exceeds what the API equations predict for that letter (API 520 5.2.5, 5.2.6).

If the required area is larger than a T orifice, the relief load has to be split between several valves; API 520's two-phase example ends with two Q orifices and one R orifice. Multiple valves use the 116 % accumulation (card 02).

LetterEffective area, in²Effective area, mm²
API 526 effective orifice areas as printed in the Baker Hughes Consolidated and LESER sizing guides; mm² = in² × 645.16. API 520 quotes the K, M, P, Q, R and T areas in its examples.
09

Notes, Limitations & Sources

This calculator does not decide the relieving rate, check inlet pressure loss or discharge piping, or size for fire heat input; API 520 Part II and API 521 cover those. Kb for balanced-bellows valves and Kw are left for you to enter from the manufacturer, since the API 520 curves (Figures 30 and 31) are typical values only. Liquid valves without capacity certification (API 520 5.9) and rupture-disk sizing by the flow-resistance method (5.11.1.3) are not covered.

The worked examples in the Configuration list load the inputs from API 520 Part I. Two of them read a factor off a figure (F₂ = 0.86 in Example 2, ηc = 0.66 in Annex C) where this page calculates it from the equation (0.855 and 0.656), so those results differ slightly from the printed ones. The SI results in API 520's examples are the USC answers converted to mm², so the SI equations, whose constants are rounded, agree with them to about 0.2 %.

Sources

Cite This Work